Commercial Building Controls : Sensors : CO2 Sensors : C7632 : C7632A1004/U
Wall Mount CO2 Sensor with no display,0-10 Vdc (fixed) output
Overview
CO2 Sensors offer a fixed 0-2000ppm & fixed 0-10Vdc output, determine ventilation need with HVAC controllers and measure CO2 concentration in ventilated spaces or ducts. Used in ventilation & AC systems to control the amount of outdoor air supplied.
Features
- Non-Dispersion-Infrared (NDIR) technology used to measure carbon dioxide gas.
- Gold-plated sensor provides long-term calibration stability.
- Fixed 0-2000ppm, fixed 0-10Vdc output.
- Used for CO2 based ventilation control (Demand Control Ventilation (DCV)).
- Automatic Background Calibration (ABC) algorithm based on long-term evaluation reduces required typical zero-drift check maintenance.
Product Specifications
- Application
- Carbon Dioxide Sensor
- Dimensions (in.)
- 4 1/8 in high x 3 7/8 in. wide x 1 1/16 in. deep
- Dimensions (mm)
- 104 mm high x 99 mm high x 27 mm deep
- Includes
- Honeywell Logo
- Item Type
- Product
- Mounting
- Wall mount
- Frequency
- 50 Hz; 60 Hz
- Electrical Connections
- Terminal block
- Sensor
- Non-dispersive Infrared (NDIR)
- Voltage
- 24 Vac (20%)
- Operating Temperature Range (F)
- 32 F to 122 F
- Operating Temperature Range (C)
- 0 C to 50 C
- Relay Outputs
- None
- Timing
- Response--1 minute
- Accuracy
- 5% full scale
- Display
- None
- Sensor Range
- 0 to 2000 ppm, fixed
- Analog Current Output
- 0-10 Vdc fixed