Distributor
Environmental & Combustion Controls
> AT175
AT175B1055
Foot mounted 120 Vac Transformer with 9 in lead wires
Locate Distributors
Product Specifications Literature and
Documents
Overview
Provide power to 24 Vac circuits in heating/cooling control systems.
Intended for use in systems with predictable, uniform loads. Can be
used in any application that does not exceed the listed ratings.
Features
o Rated at 75 VA.
o Color-coded leadwires for primary connections and screw terminals
for secondary connections, fixed 1/4 inch (6 mm) male quick-connects
or color-coded leadwires for both primary and secondary, are standard.
o Meet NEC Class 2 requirements.
o Meet Underwriters Laboratories Inc. Standard UL 1585 and are
identified. Class 2 not wet, Class 3 wet.
Product Specifications Back To Top
Description Foot mounted 120 Vac Transformer with 9 in lead wires
Electrical Ratings -Primary Voltage 120 Vac
Frequency 60 Hz
Mounting Foot-mounted
Electrical Connections (Primary)(in.) 9 in leadwires
Electrical Connections (Primary)(mm) 229 mm leadwires
Electrical Connections (Secondary)(in.) 9 in. leadwires
Electrical Connections (Secondary)(mm) 229 mm leadwires
Electrical Ratings -Output 24 Vac at 75 VA
Dimensions (in.) 2 1/3 in high x 3 9/16 in wide x 2 1/3 in deep
Dimensions (mm) 59 mm high x 90 mm wide x 68 mm deep
Temperature Ratings (F) -20 F to +105 F
Temperature Ratings (C) -29 C to +41 C
Approvals, Underwriters Laboratories Inc UL Component Recognized
Approvals, Canadian Standards Association CSA Certified:
Literature and other Resources Download
Back To Top
Installation Instructions - (AT120A, AT140A, AT150A, AT175A Universal
Transformers)
Product Data - (AT120A, AT120B, AT120C, AT120D, AT120E, AT140A,
AT140B, AT140C, AT140D, AT140E, AT150A, AT150B, AT15DE, AT15F, AT160B,
AT175A, AT175B, AT175C, AT175D Transformers)
Installation Instructions - (AT150F, AT175F Universal Circuit Breaker
Transformers -TRADELINE)
Download -Submit
Welcome
Category: SUPPLIER DIRECTORY => HONEYWELL, INC
February 2009
> AT175
Residential Comfort/Combustion : Electrical Components : Transformers : AT175 : AT175B1055/U
Foot mounted 120 Vac Transformer with 9 in lead wires
Overview
Honeywell 75 VA general purpose transformers power 24 Vac circuits.
Features
- Color-coded lead wires for primary connections and screw terminals for secondary connections
- Includes fixed 1/4 inch (6mm) male quick-connects (AT175A models only) or color-coded lead wires for primary and secondary connections
- Meets Underwriters Laboratories Standard UL 1585
- Identified Class 2 not wet, Class 3 wett
Product Specifications
- Dimensions (in.)
- 2 1/3 in high x 3 9/16 in wide x 2 1/3 in deep
- Dimensions (mm)
- 59 mm high x 90 mm wide x 68 mm deep
- Temperature Range (F)
- -20 F to +105 F
- Temperature Range (C)
- -29 C to +41 C
- Mounting
- Foot-mounted
- Electrical Ratings
- Primary voltage--120 Vac
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized
- Approvals, CSA
- CSA Certified:
- Electrical Connections (Primary)(in.)
- 9 in leadwires
- Electrical Connections (Primary)(mm)
- 229 mm leadwires
- Electrical Connections (Secondary)(in.)
- 9 in. leadwires
- Electrical Connections (Secondary)(mm)
- 229 mm leadwires
- Electrical Ratings, Output
- 24 Vac at 75 VA