Description
EATON PDG20G0225TFFL, PD2 Global Ratings, PDG2, 600 VAC, 225 A, ≤ 3 W Power, 50/60 Hz Frequency, 35 kA Interrupt, 2 Frame, T-M (Fxd-Fxd) TU Trip, 4 Pole, Load only Connection, 690 V Auxiliary, 4 to 4/0 AWG, 21.2 to 107 sq-mm Wire, IP2X Enclosure, Fixed/Plug-in/DIN Rail Mounting, -20 to +70 deg C, 6 in H x 5.5 in W x 3.5 in D Dimensions, Glass Polyester, White
Features:
- Power Xpert Release trip units offer features such as Breaker Health, multiple Load Alarms, and Ground Fault Alarm to help avoid costly downtime through predictive and preventative maintenance
- Arcflash Reduction Maintenance System helps to reduce arc flash incident energy levels, thereby reducing PPE requirements and minimizing risk while improving personnel safety and productivity
- The PXR trip units provide an intuitive user interface that allows you to easily view and adjust breaker settings and system performance
- Embedded communications and metering help to reduce cost by eliminating the need for separate communication components and associated wiring
- Field installable components and trip units minimize the amount of inventory while enabling the user almost infinite options to customize the breaker to the application and their specification
- 18 kAIC at 600V (UL/CSA), 10 kAIC Icu at 125 VDC, 25 kAIC Icu/ 20 kAIC Ics/ 52.5 kAIC Icm at 480V Brazil (IEC), 36 kAIC Icu/ 36 kAIC Ics/ 75.6 kAIC Icm at 380-415V (IEC), 30 kAIC Icu/ 22.5 kAIC Ics/ 63 kAIC Icm at 440V (IEC), 35 kAIC at 480V (UL), 55 kAIC Icu/ 55 kAIC Ics/ 121 kAIC Icm at 240V (IEC), 65 kAIC at 240V (UL), 20 kAIC Icu/ 15/13 kAIC Ics/ 42 kAIC Icm at 525V South Africa (IEC), 8 kAIC Icu/ 4 kAIC Ics/ 16.8 kAIC Icm at 690V (IEC), 10 kAIC Icu at 250 VDC interrupt rating
- Thermomagnetic switch off technique
- 0% neutral protection
Applications:
Utility - Substations, Utility Transmission and Distribution, Marine Vessels and Equipment - Marine Vessels and Equipment - Other, Renewable Energy and Alternative Energy Generation, On-Road Vehicles, Stationary Machine Equipment in Factory - Robotics, Mobile Machinery and Equipment, Electrical Assemblies, Panels and EOEMs Applications, Panels and EOEMs , Conventional Energy, Aviation, Vocational Vehicles
Standards/Approval:
- CCC Certified
- CSA Certified
- IEC 60947-2
- RoHS Compliant
- UL 489
Warranty:
1 year from the date of installation, 18 months from the date of shipment