Description
EATON PDG14P0080VFFJ, PD1 Global Ratings, PDG1, 600 V AC, 80 A, ≤ 4.3 W Power, 50/60 Hz Frequency, 100 kA Interrupt, 1 Frame, Thermal Magnetic Trip, 4 Pole, Line/Load Connection, 500 V Auxiliary, 14 to 3/0 AWG, 28 to 85 sq-mm Wire, IP30 Enclosure, Fixed/Plug-in/DIN Rail Mounting, -20 to +70 deg C, 5.5 in H x 4 in W x 3 in D Dimensions, Glass Polyester, White
Features:
- Power Xpert Release trip units offer features such as Breaker Health, multiple Load Alarms, and Ground Fault Alarm to help avoid costly downtime through predictive and preventative maintenance
- Arcflash Reduction Maintenance System helps to reduce arc flash incident energy levels, thereby reducing PPE requirements and minimizing risk while improving personnel safety and productivity
- The PXR trip units provide an intuitive user interface that allows you to easily view and adjust breaker settings and system performance
- Embedded communications and metering help to reduce cost by eliminating the need for separate communication components and associated wiring
- Field installable components and trip units minimize the amount of inventory while enabling the user almost infinite options to customize the breaker to the application and their specification
- Thermomagnetic switch off technique
- 100 kAIC Icu/ 50 kAIC Ics/ 220 kAIC Icm at 440V (IEC), 200 kAIC at 240V (UL), 100 kAIC at 480/277V (UL), 40 kAIC Icu/ 25 kAIC Ics/ 84 kAIC Icm at 525V South Africa (IEC), 200 kAIC Icu/ 150 kAIC Ics/ 440 kAIC Icm at 240V (IEC), 85 kAIC Icu/ 40 kAIC Ics/ 187 kAIC Icm at 480V Brazil (IEC), 100 kAIC Icu/ 50 kAIC Ics/ 220 kAIC Icm at 380-415V (IEC), 65 kAIC at 600/347V (UL), 35 kAIC Icu/ 18 kAIC Ics/ 73.5 kAIC Icm at 690V (IEC) interrupt rating
Applications:
Electrical Assemblies, Panels and EOEMs Applications, Panels and EOEMs
Standards/Approval:
- CCC Marked,CSA,IEC 60947-2,UL 489,RoHS Compliant