KSCdirect

Product Data

KSCdirect Part #: CH N48M28B15CUNV
Description: 15KVA K13 TENV TX 3PH 480D-208Y/120 80C N15405
MFG Part #: N48M28B15CUNV
UPC: 786680067884
Supplier: CUTLER-HAMMER INC
Variable lead time item; we expect to ship this promptly.
You will be notified of any delay and may cancel at that time.

Your Price: $31968.79 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

Description

EATON K-Factor Transformer, Type KT-13 Energy Efficient Non-Linear Non-Ventilated Totally Enclosed, 480 Delta VAC Primary, 208Y/120 VAC Secondary, 15 kVA, 60 Hz, 3 Phase , 6 Taps, Lug, 915DN Frame, 220 deg C, NEMA 2, 80 deg C, Copper Winding Material, Steel Housing, 22 in L x 29 in W x 39.18 in H

Features:

  • Includes transformers with DOE 2016 and NEMA TP-1 efficiency requirements and transformers with other efficiency requirements
  • Specially designed to withstand the harmful overheating effects caused by harmonics generated by nonlinear (non-sinusoidal) loads
  • Neutral bus size configured to accommodate at least 200% of the rated current compensates for increased neutral currents found in non-linear loads, thus reducing heat
  • Transformers include a versatile bonding/grounding bar affixed to the bottom panel as standard to provide compliance with NEC 450.10(A)
  • The core and coil assembly is grounded to the transformer enclosure by means of a visible flexible copper ground strap
  • Reduced core flux density
  • Coils designed to minimize stray losses
  • Electrostatic shield reduces transient noise in the system which may affect sensitive computer loads

Applications:

Indoor Applications

Standards/Approval:

  • UL Listed
  • NEMA ST-20
  • ANSI Specified
  • IEEE Certified
  • UBC Certified
  • IBC Certified
  • California Code Title 24 Compliant

Warranty:

1 year

Attributes/Specifications

Circuit Type 915DN Frame
Connection Type Lug
Dimensions 22 in L x 29 in W x 39.18 in H
Enclosure Type NEMA 2
Frequency Rating 60 Hz
Housing Material Steel
Insulation 220 deg C
Number of Taps 6
Phase 3
Power Rating 15 kVA
Primary Voltage 480 Delta VAC
Secondary Voltage 208Y/120 VAC
Temperature Rating 80 deg C
Type Type KT-13 Energy Efficient Non-Linear Non-Ventilated Totally Enclosed
Winding Material Copper
Manufacturer CUTLER-HAMMER INC

Supplemental Files