Description
EATON Motor Relay, Series: EMR-5000, 40 to 250 V AC, 19 to 300 V DC Supply, 5 A, 8 Inputs, 9 Outputs, Digital Input, Analog Output, LCD Display, Flush Mounting, -4 to 140 deg F, Aluminum, 8.06 in L x 9.72 in W x 8.7 in H Dimensions
Features:
- Use basic motor nameplate data to create a custom overload curve to accurately protect the motor, integral test function reduces maintenance time and expense
- Zone selective interlocking improves coordination and tripping time and saves money compared to a traditional bus differential scheme
- Programmable logic control functions to accommodate different control schemes, simplify the wiring of the starter
- Automatically detects direction of the motor and eliminates the need of switching current inputs into the relay
- Reduce trouble shooting time and maintenance costs-trip and event recording in non-volatile memory provides detailed information for analysis and system restoration, 6000 cycles of waveform capture aids in post fault analysis (viewable using Powerport-E software)
- Minimum replacement time-removable terminal blocks ideal in industrial environments
- Front USB port and Powerport-E software provides local computer access and user-friendly windows based interface for relay settings, configuration and data retrieval
- Fast and easy troubleshooting, improved maintenance procedures and increased device security, provides detailed traceability for system configuration changes
- Relays self-diagnostics and reporting improves uptime and troubleshooting
- 5/1 A phase and ground current
- PROFIBUS-DP over D-Sub/RS-485 communication
- 2 Al + 2AO, zone interlocking, URTD interface, IRIG-B, large display
Standards/Approval:
- ANSI C37.90
- BAA Compliant
- CSA C22.2 No 14-95
- EN 50178
- EN 61000-6-2
- EN 61000-6-3
- IEC 60255-6
- UL 508/File E217753