KSCdirect

Product Data

KSCdirect Part #: CH 3BR1224L125S
Description: 3 Ph/BR LC 125A MLO 12/24 CKT Al Bus
MFG Part #: 3BR1224L125S
UPC: 786676441506
Supplier: CUTLER-HAMMER INC
Variable lead time item; we expect to ship this promptly.
You will be notified of any delay and may cancel at that time.

Your Price: $779.60 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

Description

EATON Main Lug Loadcenter, 3-Phase, 120/208Y/240 VAC, 125 A, 10 kA Interrupt, 24 Circuits, BR Breaker, 3/4-Wire Wiring Configuration, 12 Spaces, 6 to 2/0 AWG Wire, Surface Mount, NEMA 1, NEMA C1 Enclosure Box, Galvanized Steel Housing, 3.88 in L x 14.31 in W x 21 in H

Features:

  • Extra 1-1/2 in knockout, larger knockout provides easier installation and time savings
  • Straight-in wiring saves labor and material
  • 1-panel for either top or bottom applications
  • 2/0 AWG lug, easily removable and can be installed in any location on the neutral bar
  • Type BR AFCI breakers, compact design for easier wiring and improved wireway access, provides a clean gutter space
  • Standard tin plated aluminum bus, excellent conductivity and corrosion resistance
  • Tangential center knockout, easier installation for conduit applications
  • Commercial grade main breaker, 25 kAIC series rated main breaker for superior protection
  • Neutral bus, easily removable for sub-panel applications
  • Bonding Z-strap, provides easy field conversion for service entrance applications
  • Steel backpan provides solid and reliable breaker mounting, single piece design for stability and durability
  • 6 to 2/0 AWG copper/aluminum wire size
  • Without feed-through lugs

Applications:

Electrical Assemblies, Panels and OEMs Applications

Standards/Approval:

  • UL 50/67
  • UL E52977

Warranty:

10 years

Attributes/Specifications

Amperage Rating 125 A
Breaker Type BR
Dimensions 3.88 in L x 14.31 in W x 21 in H
Enclosure Box Size NEMA C1
Enclosure Type NEMA 1
Housing Material Galvanized Steel
Interrupt Rating 10 kA
Mounting Type Surface
Number of Circuits 24
Number of Spaces 12
Type 3-Phase
Voltage Rating 120/208Y/240 VAC
Wire Size 6 to 2/0 AWG
Wiring Configuration 3/4-Wire