Description
Appleton® Code Master™ Jr. Explosionproof HID Luminaire, Dust-Ignitionproof Factory Sealed Integrally Ballasted, Series: CJ Series, 120 to 277 VAC, 70 W Fixture, 0.9/0.5/0.44/0.35 A Starting, 0.82/0.48/0.41/0.36 A Operating, High Pressure Sodium Lamp, 70 W Lamp, Medium Lamp Base, 1 Lamps, ANSI S62/Integral/HX-HPF Ballast, 5800 Lumens, NEMA 4X Enclosure, Bracket Mounting, Copper Free Aluminum Housing Material, Epoxy Powder Coated Housing Finish, 16-1/4 in H x 16 in W Dimensions
Features:
- Fixtures operate safely in high ambient temperatures
- Arrangement of heat producing components results in more efficient heat dissipation for cooler fixture operation
- Patented wireless design, threading of fixture unit onto mounting hood makes electrical connection (the only wiring required is attaching two wires to connection block in mounting hood)
- Connection block is easily wired loosen two screws, make wire connections and re-position connection block
- Safe, easy servicing without disconnecting any wiring, wireless fixture unit easily threads off mounting hood for convenient servicing or for immediate replacement with a stand by unit
- ACME double lead threads speed installation and fixture removal from mounting hood - only half as many turns are required as for single lead threads
- The threads do not stick or gall, eliminating problems often encountered with single lead threads during fixture unit removal
- All threaded joints are flame-tight
- Heat and impact resistant globes have smooth dust resistant exterior
- Superior corrosion resistance, with epoxy powder coated finish
- Shock-absorbing medium base socket mounts prolong lamp life and porcelain socket with nickel plated phosphor bronze screw shell
- Strategic location of lamp socket in combination with the interior prism design of the glass globe provides optimum light distribution and control
- Assures long trouble free operation in high ambient areas
- 0.9 A at 120 VAC, 0.5 A at 208 VAC, 0.44 A at 240 VAC, 0.35 A at 277 VAC starting, 0.82 A at 120 VAC, 0.48 A at 208 VAC, 0.41 A at 240 VAC, 0.36 A at 277 VAC operating
Applications:
For use in chemical and petrochemical plants, such as manufacturers of plastics, paints and thinners in refineries, and in other areas where ignitable vapors, dust, moisture and corrosive elements may be present, outdoor saltwater locations and for other wet locations, for use with threaded metal conduit
Standards/Approval:
- UL 1598, 844, E10444
- NEC: Class I, Division 1 and 2, Groups B, C, D, Class II, Division 1 and 2, Groups E, F, G, Class III
- CSA: Class I, Division 1 and 2, Groups B, C, D, Class II, Division 1 and 2, Groups E, F, G, Class III, Exd IIB + H2, CSA C22.2 No.250, C22.2 No.137, 025428
Warranty:
Limited